|
2003 IBC
The following excerpts are provided as a quick overview and may help
as a guide in the selection, specification, and layout of emergency
lighting products.

SECTION 1006
MEANS OF EGRESS ILLUMINATION
1006.1 Illumination required.
The means of egress, including the exit discharge, shall be illuminated
at all times the building space served by the means of egress is
occupied. Exceptions:
1. Occupancies in Group U. 2.
Aisle accessways in Group A.
3. Dwelling units and
sleeping units in Groups R-1, R-2, and R-3.
4. Sleeping units of Group I occupancies.
1006.3 Illumination emergency power.
The power supply for means of egress illumination shall normally be
provided by the premise's electrical supply. In the event of power
failure, an emergency electrical system shall automatically illuminate
the following areas: 1. Exit access corridors, passageways, and
aisles in rooms and spaces which require two or more means of egress. 2. Exit access corridors
and exit stairways located in buildings required to have two or more
exits.
3.
Exterior egress components at other than the level
of exit discharge until exit discharge is accomplished for buildings
required to have two or more exits.
4. Interior exit discharge elements, as permitted in
Section 1023.1, in buildings required to have two or more exits. 5.
The portion of the exterior exit discharge immediately adjacent to exit
discharge doorways in buildings required to have two or more exits.
The emergency power system shall provide power for a duration of not
less than 90 minutes and shall consist of storage batteries, unit
equipment, or an on-site generator. The installation of the emergency
power system shall be in accordance with Section 2702.
1006.4
Performance of system.
Emergency lighting facilities shall be arranged to
provide initial illumination that is at least an average of 1
foot-candle (11 lux) and a minimum at any point of 0.1 foot-candle (1
lux) measured along the path of egress at floor level. Illumination
levels shall be permitted to decline to 0.6 foot-candle (6 lux) average
and a minimum at any point of 0.06 foot-candle (0.6 lux) at the end of
the emergency lighting time duration. A maximum-to-minimum illumination
uniformity ratio of 40 to 1 shall not be exceeded.
SECTION 1011
EXIT SIGNS
1011.1 Where required.
Exits and exit access doors shall be marked by an
approved exit sign readily visible from any direction of egress travel.
Access to exits shall be marked by readily visible exit signs in cases
where the exit or the path of egress travel is not immediately visible
to the occupants. Exit sign placement shall be such that no point in an
exit access corridor is more than 100 feet (30 480 mm) or the listed
viewing distance for the sign, whichever is less, from the nearest
visible exit sign. Exceptions:
1. Exit signs are not
required in rooms or areas which require only one exit or exit access.
2. Main exterior exit doors or gates which obviously and clearly are
identifiable as exits need not have exit signs where approved by the
building official.
3. Exit signs are not required in occupancies in
Group U and individual sleeping units or dwelling units in Group R-1,
R-2, or R-3.
4. Exit signs are not required in sleeping areas in
occupancies in Group I-3. 5. In occupancies in Groups A-4 and A-5,
exit signs are not required on the seating side of vomitories or
openings into seating areas where exit signs are provided in the
concourse that are readily apparent from the vomitories. Egress lighting
is provided to identify each vomitory or opening within the seating area
in an emergency.
1011.2
Illumination.
Exit signs shall be internally or externally
illuminated. Exception:
Tactile signs required by Section 1011.3 need not be
provided with illumination.
1011.4
Internally illuminated exit signs.
Internally illuminated exit signs shall be listed and labeled and shall
be installed in accordance with the manufacturer's instructions and
Section 2702. Exit signs shall be illuminated at all times.
1011.5
Externally illuminated exit signs. Externally illuminated exit signs
shall comply with Sections 1011.5.1 through 1011.5.3. 1011.5.1
Graphics. Every exit sign and directional exit sign shall have
plainly legible letters not less than 6 inches (152 mm) high with the
principal strokes of the letters not less than 0.75 inch (19.1 mm) wide.
The word "EXIT" shall have letters having a width not less than 2 inches
(51 mm) wide except the letter "I", and the minimum spacing between
letters shall not be less then 0.375 inch (9.5 mm). Signs larger than
the minimum established in this section shall have letter widths,
strokes, and spacing in proportion to their height. The word "EXIT"
shall be in high contrast with the background and shall be clearly
discernible when the exit sign illumination means is or is not
energized. If an arrow is provided as part of the exit sign, the
construction shall be such that the arrow direction cannot be readily
changed. 1011.5.2
Exit sign illumination. The face of an exit sign illuminated from an
external source shall have an intensity of not less than 5 foot-candles
(54 lux). 1011.5.3 Power source. Exit signs shall be
illuminated at all times. To ensure continued illumination for a
duration of not less than 90 minutes in case of primary power loss, the
sign illumination means shall be connected to an emergency power system
provided from storage batteries, unit equipment, or an on-site
generator. The installation of the emergency power system shall be in
accordance with Section 2702. Exception:
Approved exit sign illumination means that provide continuous
illumination independent of external power sources for a duration of not
less than 90 minutes, in case of primary power loss, are not required to
be connected to an emergency electrical system.
SECTION 1023 EXIT DISCHARGE 1023.6
Access to a public way. The exit discharge shall provide a direct
and unobstructed access to a public way. Exception: Where
access to a public way cannot be provided, a safe dispersal area shall
be provided where all of the following are met:
1. The area shall be of a
size to accommodate at least 5 square feet (0.28m2)for each
person. 2.
The area shall be located on the same property at least 50 feet (15 240
mm) away from the building requiring egress.
3. The are shall be permanently maintained and
identified as a safe dispersal area.
4. The area shall be provided with a safe and
unobstructed path of travel from the building.
Copyright 2003

272 West Stag Park Service Road Burgaw, NC 28425 phone:
(910) 259-1131 | fax: (800) 403-6927
© Copyright 2006-2010 | LightGuard is a Philips group brand | All rights reserved
web design and web hosting by cfwebmasters.com
|