Brillare

 

 

Hallway Typical

 

Click on images for full page view

 

 

 

Ambient Lighting Area Summary: 

90 foot hallway emergency fixtures on 50 foot centers

 

0o Tilt

 

 

0o Tilt  Thermal

 

 

 

 

 

 

 

Emergency Mode Area Summary:

Illuminance Value (fc)

Average = 1.13

Maximum = 2.8

Minimum = 0.3

Average/Min Ratio = 3.77

Max/Min Ration = 9.33

 

5o Tilt  

 

 

5o Tilt Thermal 

 

10o Tilt

 

 

 

10o Tilt Thermal

 

 

 

Typical installation shown.  Unit Mounting Heights is 7 1/2 feet above finished floor.  Standard reflectance's 80/50/20 were used.  LightGuard is not responsible for site specific conditions that may alter the results. 